ABB RELION REX640 Technical Manual page 773

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.3.6.1
Identification
Function description
High-impedance differential protec-
tion for phase A
High-impedance differential protec-
tion for phase B
High-impedance differential protec-
tion for phase C
4.3.6.2
Function block
Figure 438: Function block
4.3.6.3
Functionality
The high-impedance differential protection function HIxPDIF is a general differential
protection. It provides a phase-segregated short circuit protection for the busbar.
However, the function can also be used for providing generator, motor, transformer
and reactor protection.
The function starts and operates when the differential current exceeds the set limit.
The operate time characteristics are according to definite time (DT).
The function contains a blocking functionality. It is possible to block the function
outputs, timer or the whole function.
4.3.6.4
Analog channel configuration
HIxPDIF has one analog group input which must be properly configured.
Table 696: Analog inputs
Input
I3P
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
REX640
Technical Manual
See the preprocessing function blocks in this document for the possible
signal sources.
IEC 61850
IEC 60617
identification
identification
HIAPDIF
dHi_A>
HIBPDIF
dHi_B>
HICPDIF
dHi_C>
Description
Three-phase currents
Protection functions
ANSI/IEEE C37.2
device number
87_A
87_B
87_C
773