Generator Shaft Current Leakage Protection Gslptoc ( Ansi 38,51) - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.1.12
Generator shaft current leakage protection GSLPTOC
( ANSI 38,51)
4.1.12.1
Identification
Function description
Generator shaft current leakage
protection
4.1.12.2
Function block
Figure 248: Function block
4.1.12.3
Functionality
Generator shaft current leakage protection function GSLPTOC protects the
generator rotor bearings from damage caused by the shaft leakage current.
The function compares measured shaft current to the set alarm and operate levels.
Operate time characteristics are according to definite time (DT).
4.1.12.4
Analog channel configuration
GSLPTOC has one analog input which must be properly configured.
Table 495: Analog inputs
Input
ISHFT
4.1.12.5
Operation principle
The
the function is enabled and respectively "Off" means function is disabled.
The operation of
using a module diagram (see figure below). All the modules in the diagram are
explained in the next sections.
REX640
Technical Manual
Operation setting is used to enable or disable the function. When selected "On"
Generator shaft current leakage protection can be described by
IEC 61850
IEC 60617
identification
identification
GSLPTOC
I>,GS
Description
Measured shaft current
Protection functions
ANSI/IEEE C37.2
device number
38, 51
435