ABB RELION REX640 Technical Manual page 439

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.1.12.8
GSLPTOC Settings
Table 498: GSLPTOC Group settings (Basic)
Parameter
Values (Range)
Sel operate har-
1=Fundamental
monic
3=Third harmonic
5=Fifth harmonic
Alarm start value
0.10...10.00
Operate start value 0.10...10.00
Alarm delay time
40...30000
Operate delay time
40...30000
Table 499: GSLPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Reset delay time
0...10000
4.1.12.9
GSLPTOC Monitored data
Table 500: GSLPTOC Monitored data
Name
Type
I_SHAFT
FLOAT32
I_SHAFT_H1
FLOAT32
I_SHAFT_H3
FLOAT32
I_SHAFT_H5
FLOAT32
START_DUR
FLOAT32
GSLPTOC
Enum
REX640
Technical Manual
Unit
Step
A
0.01
A
0.01
ms
10
ms
10
Unit
Step
ms
1
Values (Range)
0.00...10.00
0.00...10.00
0.00...10.00
0.00...10.00
0.00...100.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection functions
Default
1=Fundamental
0.25
0.50
3000
3000
Default
1=on
1000
Unit
Description
A
Amplitude of the meas-
ured shaft current
A
Amplitude of the funda-
mental component of
the measured shaft cur-
rent
A
Amplitude of the third
harmonic component
of the measured shaft
current
A
Amplitude of the fifth
harmonic component
of the measured shaft
current
%
Ratio of start time / op-
erate time
Status
Description
Select operating
harmonic
Alarm start value
Operate start value
Alarm delay time
Operate delay time
Description
Operation Off / On
Reset delay time
439