Protection functions
Start of operation timer
OPR_FRG
OPR_FRQ
OPERATE
Figure 517: Load-shedding operation in the "Freq< AND df/dt>" mode when both
Freq< and df/dt conditions are satisfied ( Rated frequency=50 Hz)
932
Frequency
[Hz]
50 Hz
49 Hz
48.75 Hz
ST_FRG
500ms
ST_FRQ
Start value Freq set at 0.975 xFn
Start value df/dt set at -0.020 xFn/s
Operate Tm df/dt = 500ms
Operate Tm Freq = 1000ms
Load shed mode = Freq< AND df/dt
1s
Start of operation timer
OPERATE is activated
as Freq< AND df/dt
condition satisfied
1MRS759142 F
Time [s]
1s
REX640
Technical Manual