ABB RELION REX640 Technical Manual page 572

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
The START output is activated once
not valid in the "Alarming EF" mode. Reset timer is started if any of the above three
conditions are not valid. In case the fault is transient and self-extinguishes, START
output stays activated until the elapse of reset timer (setting
Figure 329: Operation in "Alarming EF" mode
Intermittent EF
572
If detection of temporary earth faults is not desired, the activation of
START output can be delayed with setting
To keep the operate timer activated between current spikes during
intermittent or restriking earth fault, the
set above the maximum expected time interval between fault spikes
(obtained at full resonance condition). The recommended value is at least
300 ms.
Start delay time has elapsed. OPERATE output is
Start delay time .
Reset delay time should be
1MRS759142 F
Reset delay time ).
REX640
Technical Manual