Protection functions
Parameter
Values (Range)
8=Clk Num 8
10=Clk Num 10
11=Clk Num 11
CT ratio correction
0.200...5.000
CT connection type 1=Type 1
2=Type 2
Zro A elimination
1=Not eliminated
2=Winding 1
3=Winding 2
4=Winding 1 and 2
Restraint mode
1=None
2=Harmonic2
Table 651: LNPLDF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Minimum operate
45...60000
time
4.3.1.10
LNPLDF Monitored data
Table 652: LNPLDF Monitored data
Name
Type
START_DUR
FLOAT32
I_AMPL_LOC_A
FLOAT32
I_AMPL_LOC_B
FLOAT32
I_AMPL_LOC_C
FLOAT32
I_AMPL_REM_A
FLOAT32
I_AMPL_REM_B
FLOAT32
I_AMPL_REM_C
FLOAT32
ID_A
FLOAT32
ID_B
FLOAT32
ID_C
FLOAT32
IB_A
FLOAT32
IB_B
FLOAT32
IB_C
FLOAT32
Table continues on the next page
678
Unit
Step
0.001
Unit
Step
ms
1
ms
1
Values (Range)
0.00...100.00
0.00...40.00
0.00...40.00
0.00...40.00
0.00...40.00
0.00...40.00
0.00...40.00
0.00...80.00
0.00...80.00
0.00...80.00
0.00...80.00
0.00...80.00
0.00...80.00
Default
1.000
1=Type 1
1=Not eliminated
1=None
Default
0
45
Unit
Description
%
Ratio of start time / op-
erate time
xIr
Local phase A ampli-
tude after correction
xIr
Local phase B ampli-
tude after correction
xIr
Local phase C ampli-
tude after correction
xIr
Remote phase A ampli-
tude after correction
xIr
Remote phase B ampli-
tude after correction
xIr
Remote phase C ampli-
tude after correction
xIr
Differential current
phase A
xIr
Differential current
phase B
xIr
Differential current
phase C
xIr
Stabilization current
phase A
xIr
Stabilization current
phase B
xIr
Stabilization current
phase C
1MRS759142 F
Description
Local phase current
transformer ratio
correction
CT connection
type. Determined
by the directions of
the connected cur-
rent transformers.
Elimination of the
zero-sequence cur-
rent
Selects what re-
straint modes are
in use
Description
Reset delay time
for stabilized stage
Minimum operate
time for stabilized
stage IDMT curves
REX640
Technical Manual