Received GOOSE test mode QTY_GOOSE_TEST

3.19.3.1
Function block
Figure 104: Function block
3.19.3.2
Functionality
The GOOSE test mode function QTY_GOOSE_TEST determines whether test mode
is used between two relays communicating over GOOSE. The conditions needed for
enabling the test mode differ in both editions 1 and 2 of the IEC 61850 standard. For
more information, see the IEC 61850 engineering guide.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the test mode status of the GOOSE function block. When
the output is in the true (1) state, the GOOSE test mode is active. The value false (0)
indicates that the test mode is not in use.
3.19.3.3
Signals
Table 159: QTY_GOOSE_TEST Input signals
Name
IN
Table 160: QTY_GOOSE_TEST Output signals
Name
OUT
REX640
Technical Manual
Type
Default
Any
0
Type
Description
BOOLEAN
Output signal
Type
Default
Any
0
Type
Description
BOOLEAN
Output signal
Basic functions
Description
Input signal
Description
Input signal
215