Hotline Tag Hltgapc - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
3.20.14.7
PCGAPC Settings
Table 253: PCGAPC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Count criteria
1=Freeze
2=Rising edge
3=Falling edge
4=On change
Unit selection
1=Count
71=Apparent ener-
gy
72=Active energy
73=Reactive energy
Impulse ratio
1...9999
Impulse ratio prefix 0=No prefix
3=k
6=M
Pulse quantity
0.0001...90000.000
0
Reporting interval
0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
3.20.14.8
PCGAPC Monitored data
Table 254: PCGAPC Monitored data
Name
Type
COUNT_VALUE
INT64
SCALED_VALUE
FLOAT32
3.20.15

Hotline tag HLTGAPC

3.20.15.1
Identification
Function description
Hotline tag
REX640
Technical Manual
Unit
Step
1
0.0001
Values (Range)
0...2147483647
0.0000...1000.0000
IEC 61850
identification
HLTGAPC
Default
1=on
2=Rising edge
1=Count
1
0=No prefix
1.0000
0=1 minute
Unit
Description
da
Actual pulse counter
value
Scaled value derived
from COUNT_VALUE
IEC 60617
identification
HLTGAPC
Basic functions
Description
Operation Off / On
Pulse counter crite-
ria
Measured quantity
for SCALED_VALUE
output
Energy meter con-
stant
Prefix for unit of
impulse ratio
Factor to be
multiplied with
COUNT_VALUE
Reporting interval
for counter value
ANSI/IEEE C37.2
device number
HLTGAPC
271