ABB RELION REX640 Technical Manual page 874

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
PSPTOV Output signals
Table 815: PSPTOV Output signals
Name
OPERATE
START
4.5.4.8
PSPTOV Settings
Table 816: PSPTOV Group settings (Basic)
Parameter
Values (Range)
Start value
0.400...1.600
Operate delay time
40...120000
Table 817: PSPTOV Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 818: PSPTOV Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Relative hysteresis
1.0...5.0
4.5.4.9
PSPTOV Monitored data
Table 819: PSPTOV Monitored data
Name
Type
START_DUR
FLOAT32
PSPTOV
Enum
4.5.4.10
Technical data
Table 820: PSPTOV Technical data
Characteristic
Operation accuracy
Table continues on the next page
874
Type
BOOLEAN
BOOLEAN
Unit
Step
xUn
0.001
ms
10
Unit
Step
Unit
Step
ms
1
%
0.1
Values (Range)
0.00...100.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the voltage measured:
f
n
±1.5% of the set value or ±0.002 × U
Description
Operate
Start
Default
0.650
40
Default
1=on
Default
20
4.0
Unit
Description
%
Ratio of start time / op-
erate time
Status
1MRS759142 F
Description
Start value
Operate delay time
Description
Operation Off / On
Description
Reset delay time
Relative hysteresis
for operation
n
REX640
Technical Manual