ABB RELION REX640 Technical Manual page 445

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Table 505: Reset time characteristics supported by different stages
Reset curve type
(1) Immediate
(2) Def time reset
(3) Inverse reset
4.2.1.8
Application
EFxPTOC is designed for protection and clearance of earth faults in distribution
and sub-transmission networks where the neutral point is isolated or earthed
via a resonance coil or through low resistance. It also applies to solidly earthed
networks and earth-fault protection of different equipment connected to the power
systems, such as shunt capacitor bank or shunt reactors and for backup earth-fault
protection of power transformers.
Many applications require several steps using different current start levels and time
delays. EFxPTOC consists of three different protection stages.
• Low EFLPTOC
• High EFHPTOC
• Instantaneous EFIPTOC
EFLPTOC contains several types of time-delay characteristics. EFHPTOC and
EFIPTOC are used for fast clearance of serious earth faults.
4.2.1.9
Signals
EFLPTOC Input signals
Table 506: EFLPTOC Input signals
Name
IRES
BLOCK
ENA_MULT
REX640
Technical Manual
EFLPTOC
x
x
x
Type of reset curve setting does not apply to EFIPTOC or when the
The
DT operation is selected. The reset is purely defined by the
time setting.
Type
SIGNAL
BOOLEAN
BOOLEAN
EFHPTOC
Note
x
Available for all operate time curves
x
Available for all operate time curves
x
Available only for ANSI and user pro-
grammable curves
Default
-
0=False
0=False
Protection functions
Reset delay
Description
Residual current
Block signal for acti-
vating the blocking
mode
Enable signal for cur-
rent multiplier
445