ABB RELION REX640 Technical Manual page 975

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
three-phase impedance element have been modified. These zone settings should
be checked to see whether a non-zero TLT_ANG_CONFLICT value has been found
although, internally, the polygon boundary has been closed for existing settings.
Directional lines
The direction of a zone is defined with setting
"Nondirectional", "Forward" or "Reverse". The directionality of each zone can be
set independently of other zones. For example, zones Z1 and Z2 can be set in the
"Forward" direction and Z3 in the "Reverse" direction. Furthermore, the optionally
supervised earth-fault directional criteria (in low-impedance earthed networks)
given for GFC are checked here together with zone direction criteria fulfilment.
The directionality of a quadrilateral zone is defined with two independent
directional lines. The directional lines can be included into the mho characteristics
to secure the directionality or to transform the non-directional mho characteristic
into a directional one.
The directional lines are adjusted with the
angle zone settings, which are common for all the zones. The angles are given in
degrees. The directional lines are polarized with the
default, the polarization method is positive-sequence voltage ("Pos. seq. volt.").
Directional mode Znx = Forward
Min phase angle zone
Figure 549: Settings that adjust directional lines in case of quadrilateral
characteristics
The calculated direction of the fault or load (if there is no fault present) current
is indicated for each zone with outputs DIRECTION_Z1 - Z5 which may have values
"unknown", "forward", "backward" or "both". It is important to check setting
reverse zone x (or Z1 reverse zone x reactance part) for quadrilateral directional
characteristics (see
given in
by settings
Memory voltage
The memory voltage is based on the healthy positive-sequence voltage stored
during the network healthy state. This fictive voltage is substituted for the
measured voltage with any impedance measurement element polarization if
the corresponding voltage drops too low (limit is 5% Un). Fictive voltage use
is indicated by the active monitored data output VMEM_USED. The polarized
impedance direction for a corresponding impedance element is frozen after a
fixed 100 ms of fictive voltage use, but the memory function enables impedance
polarization to operate up to a maximum of 300 s. This time can be set with the
REX640
Technical Manual
X
Forward
R
Max phase angle zone
Figure 541
Figure 543
) so that it does not restrict the negative-reactance reach defined
Min Ris Gnd/PP Rch Znx and Max phase angle zone.
Directional mode Znx =
Min phase angle zone and Max phase
Pol quantity zone method. By
Directional mode Znx = Reverse
Max phase angle zone
Reverse
and the corresponding phase-to-earth impedance
Protection functions
X
R
Min phase angle zone
X1
975

Advertisement

Table of Contents
loading

Table of Contents