ABB RELION REX640 Technical Manual page 693

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Figure 394: Operating characteristics of the protection. (LS) stands for the biased
low stage and (HS) for the instantaneous high stage
The OPERATE output is activated always when the OPR_HS output activates .
The internal blocking signals of the differential function do not prevent the operate
signal of the instantaneous differential current stage. When required, the operate
outputs of the instantaneous high stage can be blocked by the BLK_OPR_HS and
BLOCK external control signals.
Figure 395: Operation logic of instantaneous high stage
Reset of the blocking signals (de-block)
All three blocking signals, that is, waveform and second and fifth harmonic, have a
counter, which holds the blocking on for a certain time after the blocking conditions
have ceased to be fulfilled. The deblocking takes place when those counters have
elapsed. This is a normal case of deblocking.
The blocking signals can be reset immediately if a very high differential current is
measured or if the phase difference of the compared currents (the angle between
the compared currents) is close to zero after the automatic vector group matching
has been made (in a normal situation, the phase difference is 180 degrees). This
REX640
Technical Manual
Protection functions
693