ABB RELION REX640 Technical Manual page 366

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Parameter
Values (Range)
3=3 out of 3
Table 409: DPHHPDOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Minimum operate
20...60000
time
Allow Non Dir
0=False
1=True
Measurement
1=RMS
mode
2=DFT
3=Peak-to-Peak
Min operate current 0.01...1.00
Min operate volt-
0.01...1.00
age
4.1.2.11
Monitored data
DPHLPDOC Monitored data
Table 410: DPHLPDOC Monitored data
Name
Type
START_DUR
FLOAT32
DIR_A
Enum
DIR_B
Enum
DIR_C
Enum
ANGLE_A
FLOAT32
ANGLE_B
FLOAT32
ANGLE_C
FLOAT32
VMEM_USED
BOOLEAN
DPHLPDOC
Enum
366
Unit
Step
Unit
Step
ms
1
ms
1
xIn
0.01
xUn
0.01
Values (Range)
0.00...100.00
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
-180.00...180.00
-180.00...180.00
-180.00...180.00
0=False
1=True
1=on
2=blocked
3=test
Default
Default
20
20
0=False
2=DFT
0.01
0.01
Unit
Description
%
Ratio of start time / op-
erate time
Direction phase A
Direction phase B
Direction phase C
deg
Calculated angle differ-
ence, Phase A
deg
Calculated angle differ-
ence, Phase B
deg
Calculated angle differ-
ence, Phase C
Voltage memory in use
status
Status
1MRS759142 F
Description
Description
Reset delay time
Minimum operate
time for IDMT
curves
Allows prot activa-
tion as non-dir
when dir info is in-
valid
Selects used meas-
urement mode
Minimum operating
current
Minimum operating
voltage
REX640
Technical Manual