ABB RELION REX640 Technical Manual page 432

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
and long-time thermal history, allowing more critical situations like motor start-ups
to be taken into consideration more carefully.
Setting of thermal restart level
The
= 100% −
For instance, if the start-up time of the motor is 4 seconds, and the calculated
operate time of the thermal protection stage for cold motor is 6 seconds, one
motor start-up will use 4/6 = 66.6% of the thermal capacity of the motor. Therefore,
the
(100% - (66.6% + margin), where margin is 5%).
Setting of thermal alarm level
Tripping due to high overload can be avoided by reducing the load of the motor
when the thermal level reaches a set alarm level.
The
full thermal capacity without causing a trip due to long time overload. Generally, the
Alarm thermal value is set to 80....90% of the trip level.
4.1.11.7
Signals
RPTTR Input signals
Table 488: RPTTR Input signals
Name
I3P
U3P
BLOCK
START_EMERG
AMB_TEMP
432
Restart thermal Val can be calculated as follows:
(
Restart thermal Val must be set to below 100% - 66.6% = 33.3% say to 28.3%
Alarm thermal value can be set to a level, which will allow the use of the motor's
Type
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
FLOAT32
)
∙ 100% +
Default
-
-
0=False
0=False
0
1MRS759142 F
(Equation 55)
Description
Three-phase currents
Three-phase voltages
Block signal for acti-
vating the blocking
mode
Signal for indicating
the need for emer-
gency start
The ambient temper-
ature used in the cal-
culation
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents