ABB RELION REX640 Technical Manual page 409

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.1.9.8
Settings
Table 470: PHPTUC Group settings (Basic)
Parameter
Values (Range)
Current block value 0.00...0.50
Start value
0.01...1.00
Operate delay time
50...200000
Table 471: PHPTUC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Operation mode
1=Three Phase
2=Single Phase
Table 472: PHPTUC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.1.9.9
Monitored data
Table 473: PHPTUC Monitored data
Name
START_DUR
PHPTUC
4.1.9.10
Technical data
Table 474: PHPTUC Technical data
Characteristic
Operation accuracy
Table continues on the next page
REX640
Technical Manual
Unit
Step
xIn
0.01
xIn
0.01
ms
10
Unit
Step
Unit
Step
ms
1
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection functions
Default
0.10
0.50
2000
Default
1=on
1=Three Phase
Default
20
Unit
%
Value
Depending on the frequency of the current
measured: f
±2 Hz
n
±1.5% of the set value or ± 0.002 × I
Description
Low current setting
to block internally
Current setting to
start
Operate delay time
Description
Operation Off / On
Number of phases
needed to start
Description
Reset delay time
Description
Ratio of start
time / operate
time
Status
n