ABB RELION REX640 Technical Manual page 362

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
DPHHPDOC Input signals
Table 399: DPHHPDOC Input signals
Name
I3P
U3P
BLOCK
ENA_MULT
NON_DIR
DPHLPDOC Output signals
Table 400: DPHLPDOC Output signals
Name
OPERATE
START
FAULT_DIR
DIRECTION
DPHHPDOC Output signals
Table 401: DPHHPDOC Output signals
Name
OPERATE
START
FAULT_DIR
DIRECTION
4.1.2.10
Settings
DPHLPDOC Settings
Table 402: DPHLPDOC Group settings (Basic)
Parameter
Values (Range)
Start value
0.05...10.00
Start value Mult
0.8...10.0
Time multiplier
0.025...15.000
Table continues on the next page
362
Type
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
Enum
Enum
Type
BOOLEAN
BOOLEAN
Enum
Enum
Unit
Step
xIn
0.01
0.1
0.005
Default
Description
-
Three-phase currents
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
0=False
Enable signal for cur-
rent multiplier
0=False
Forces protection to
non-directional
Description
Operate
Start
Detected fault direction
Direction information
Description
Operate
Start
Detected fault direction
Direction information
Default
0.05
1.0
1.000
1MRS759142 F
Description
Start value
Multiplier for scal-
ing the start value
Time multiplier
in IEC/ANSI IDMT
curves
REX640
Technical Manual