1MRS759142 F
Table 366: Proposed functionality of numerical transformer and busbar overcur-
rent protection. DT = definite time, IDMT = inverse definite minimum time
O/C-stage
HV/3I>
HV/3I>>
HV/3I>>>
LV/3I>
LV/3I>>
LV/3I>>>
In case the bus-tie breaker is open, the operating time of the blockable overcurrent
protection is approximately 100 ms (relaying time). When the bus-tie breaker is
closed, that is, the fault current flows to the faulted section of the busbar from two
directions, the operation time becomes as follows: first the bus-tie relay unit trips
the tie breaker in the above 100 ms, which reduces the fault current to a half. After
this the incoming feeder relay unit of the faulted bus section trips the breaker in
approximately 250 ms (relaying time), which becomes the total fault clearing time in
this case.
Figure 202: Numerical overcurrent protection functionality for a typical sub-
transmission/distribution substation (feeder protection not shown). Blocking
output = digital output signal from the start of a protection stage, Blocking in =
digital input signal to block the operation of a protection stage
The operating times of the time selective stages are very short, because the grading
margins between successive protection stages can be kept short. This is mainly due
to the advanced measuring principle allowing a certain degree of CT saturation,
good operating accuracy and short retardation times of the numerical units. So, for
REX640
Technical Manual
Operating char.
Selectivity mode
DT/IDMT
time selective
DT
blockable/time
selective
DT
current selective
DT/IDMT
time selective
DT
time selective
DT
blockable
Protection functions
Operation speed
Sensitivity
low
very high
high/low
very high
low
very high
low
high
high
low
high