Protection functions
Figure 213: Two-phase short circuit, short circuit is between phases B and C
Negative sequence voltage as polarizing quantity
When the negative voltage is used as the polarizing quantity, the angle difference
between the operating and polarizing quantity is calculated with the same formula
for all fault types:
ANGLE X
This means that the actuating polarizing quantity is - U
356
The equations are valid when network rotating direction is counter-
clockwise, that is, ABC. If the network rotating direction is reversed,
180 degrees is added to the calculated angle difference. This is done
automatically with a system parameter
_
(
U
)
( )
I
ϕ
ϕ
ϕ
=
−
−
−
2
2
Phase rotation .
RCA
1MRS759142 F
(Equation 21)
.
2
REX640
Technical Manual