Iec 101-104 Secure Settings - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Parameter
Values (Range)
Single Char Resp
0=False
1=True
Show Bad Time
0=False
1=True
Time Format
1=Full 56bit
Time Zone
0=Local
1=UTC
Overflow Mode
0=Oldest+indica-
tion
1=Keep newest
OvInd IOA
0...16777215
OvInd NoGI IOA
0...16777215
Selection Timeout
1...65
Counter Reporting
0=Read by master
1=Spontaneous
Freeze mode
0=Not in use
1=Freeze only
2=Freeze and Reset
TX window (k)
1...20
RX window (w)
1...20
TX timeout (t1)
1...2147483647
RX timeout (t2)
1...2147483647
Test interval (t3)
0...2147483647
Cyclical Period
1...604800
IT_FRZ
0=False
1=True
Command delay
0...65535
Prtl Customization
0...2147483647
3.1.12

IEC 101-104 Secure settings

64
Unit
Step
1
1
s
1
1
1
ms
1
ms
1
ms
1
s
1
ms
1
1
1MRS759142 F
Default
Description
0=False
Single character
response ena-
bled/disabled
1=True
Enable/disable bad
time quality indica-
tion in events
1=Full 56bit
Time stamp format
3 or 7 octet
1=UTC
Selects between
UTC/Local time
0=Oldest+indica-
Event buffer over-
tion
flow handling
mechanism
60000
Overflow indication
address for interro-
gated data
60000
Overflow indication
address for non-in-
terrogated data
30
Selection timeout
for control SBO op-
erations
0=Read by master
Counter reporting
after freeze
0=Not in use
Freezing mode for
externally triggered
integrated totals
12
IEC60870-5-104
transmit window
(k)
8
IEC60870-5-104 re-
ceive window (w)
30000
IEC60870-5-104
transmit timeout
(t1)
10000
IEC60870-5-104 re-
ceive timeout (t1)
20000
IEC60870-5-104 link
test interval (t3) - 0:
Disables the trans-
mission of test
frames
10
Cyclical period in
seconds
0=False
Control point for
freezing integrated
totals
5000
Maximum delay for
timestamped com-
mands in millisec-
onds.
0
Customization pa-
rameter. Please, re-
fer to the protocol
manual.
Technical Manual
REX640

Advertisement

Table of Contents
loading

Table of Contents