ABB RELION REX640 Technical Manual page 476

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
DEFHPDEF Output signals
Table 542: DEFHPDEF Output signals
Name
OPERATE
START
FAULT_DIR
DIRECTION
4.2.2.12
Settings
DEFLPDEF Settings
Table 543: DEFLPDEF Group settings (Basic)
Parameter
Values (Range)
Start value
0.010...10.000
Start value Mult
0.8...10.0
Directional mode
1=Non-directional
2=Forward
3=Reverse
Time multiplier
0.025...15.000
Operating curve
1=ANSI Ext. inv.
type
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Operate delay time
50...300000
Characteristic an-
-179...180
gle
Max forward angle
0...180
Table continues on the next page
476
Type
BOOLEAN
BOOLEAN
Enum
Enum
Unit
Step
xIn
0.005
0.1
0.005
ms
10
deg
1
deg
1
1MRS759142 F
Description
Operate
Start
Detected fault direction
Direction information
Default
Description
0.010
Start value
1.0
Multiplier for scal-
ing the start value
2=Forward
Directional mode
1.000
Time multiplier
in IEC/ANSI IDMT
curves
15=IEC Def. Time
Selection of time
delay curve type
50
Operate delay time
-90
Characteristic an-
gle
80
Maximum phase
angle in forward di-
rection
Technical Manual
REX640