Protection functions
Table 659: TR2PTDF Group settings (Advanced)
Parameter
Values (Range)
Enable high set
0=False
1=True
Slope section 3
10...100
Harmonic deblock
0=False
2.
1=True
Stop value 5.H
10...50
Harmonic deblock
0=False
5.
1=True
Table 660: TR2PTDF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
CT connection type 1=Type 1
2=Type 2
Winding 1 type
1=Y
2=YN
3=D
4=Z
5=ZN
Winding 2 type
1=y
2=yn
3=d
4=z
5=zn
Clock number
0=Clk Num 0
1=Clk Num 1
2=Clk Num 2
4=Clk Num 4
5=Clk Num 5
6=Clk Num 6
7=Clk Num 7
8=Clk Num 8
10=Clk Num 10
11=Clk Num 11
Zro A elimination
1=Not eliminated
2=Winding 1
3=Winding 2
4=Winding 1 and 2
CT ratio Cor Wnd 1
0.40...4.00
CT ratio Cor Wnd 2
0.40...4.00
712
Unit
Step
%
1
%
1
Unit
Step
0.01
0.01
1MRS759142 F
Default
Description
1=True
Enable high set
stage
100
Slope of the third
line of the operat-
ing characteristics
1=True
2. harmonic de-
blocking in case of
switch on to fault
35
5. harmonic de-
blocking ratio
0=False
5. harmonic de-
blocking in case of
severe overvoltage
Default
Description
1=on
Operation Off/On
1=Type 1
CT connection
type. Determined
by the directions of
the connected cur-
rent transformers
1=Y
Connection of the
HV side windings
1=y
Connection of the
LV side windings
0=Clk Num 0
Setting the phase
shift between HV
and LV with clock
number for connec-
tion group com-
pensation (e.g.
Dyn11 -> 11)
1=Not eliminated
Elimination of the
zero-sequence cur-
rent
1.00
CT ratio correction,
winding 1
1.00
CT ratio correction,
winding 2
Technical Manual
REX640