ABB RELION REX640 Technical Manual page 365

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Operate delay time
40...300000
Characteristic an-
-179...180
gle
Max forward angle
0...90
Max reverse angle
0...90
Min forward angle
0...90
Min reverse angle
0...90
Table 407: DPHHPDOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Voltage Mem time
0...3000
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
Table 408: DPHHPDOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Num of start pha-
1=1 out of 3
ses
2=2 out of 3
REX640
Technical Manual
Unit
Step
ms
10
deg
1
deg
1
deg
1
deg
1
deg
1
Unit
Step
ms
1
Unit
Step
0.0001
0.0001
0.01
0.01
0.1
Protection functions
Default
Description
40
Operate delay time
60
Characteristic an-
gle
80
Maximum phase
angle in forward di-
rection
80
Maximum phase
angle in reverse di-
rection
80
Minimum phase an-
gle in forward di-
rection
80
Minimum phase an-
gle in reverse direc-
tion
Default
Description
1=Immediate
Selection of reset
curve type
40
Voltage memory
time
5=Cross pol
Reference quantity
used to determine
fault direction
Default
Description
1=on
Operation Off / On
28.2000
Parameter A for
customer program-
mable curve
0.1217
Parameter B for
customer program-
mable curve
2.00
Parameter C for
customer program-
mable curve
29.10
Parameter D for
customer program-
mable curve
1.0
Parameter E for
customer program-
mable curve
1=1 out of 3
Number of phases
required for oper-
ate activation
365

Advertisement

Table of Contents
loading

Table of Contents