Hmi Control Settings - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Table 13: Non group settings
Parameter
Values (Range)
FB naming conven-
1=IEC61850
tion
2=IEC60617
3=ANSI
1
Backlight timeout
1...60
Web HMI mode
0=Off
1=On
HMI timeout
1...60
SLD symbol format 1=IEC
2=ANSI
Setting visibility
1=Basic
2=Advanced
User defined name
0=Disabled
1=Enabled
3.1.8

HMI control settings

Confirmation dialog
If the parameter
confirmation", a confirmation dialog box opens after tapping the control button.
The confirmation dialog box has a progress bar indicating the
the controllable object. If the
"sbo-with-enhanced-security", the confirmation dialog box always opens regardless
of the
Delayed close
If the parameter
use", a timer is started after tapping the close button and accepting the possible
confirmation dialog. Close operation is performed only after the timer reaches zero.
Remaining time is displayed on top of close button, user can cancel the operation
during countdown by tapping the Cancel button. The delay can be configured by
Close delay in Configuration > Control > LHMI.
Table 14: HMI control settings
Parameter
Close delay
mode
Table continues on the next page
1
SHMI has separate backlight timeout setting that is used while in switchgear view. The SHMI
setting can be accessed from SHMI settings page, that is available while in SHMI's switchgear
page.
60
Unit
min
min
Breaker operation in Configuration > Control > HMI is set to "After
Breaker operation setting value.
Close delay mode in Configuration > Control > LHMI is set to "In
Values
1=In use
2=Not in use
Step
Default
1=IEC61850
1
3
0=Off
1
3
1=IEC
2=Advanced
false
Control mode setting of a control function is set to
Unit
Step
Default
2=Not in use
1MRS759142 F
Description
FB naming conven-
tion used in IED
LHMI backlight
timeout
Web HMI function-
ality
HMI login timeout
Single Line Dia-
gram symbol for-
mat
Setting visibility for
HMI
Configuration of
User defined name
Select timeout set for
Description
Delayed operation
when closing circuit
breakers, disconnec-
REX640
Technical Manual