ABB RELION REX640 Technical Manual page 346

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Table 390: Special conditions
Condition
U3P connected to real measurements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.1.2.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of DPHxPDOC can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
NON_DIR
ENA_MULT
Figure 206: Functional module diagram
Directional calculation
The directional calculation compares the current phasors to the polarizing phasor.
A suitable polarization quantity can be selected from the different polarization
quantities, which are the positive sequence voltage, negative sequence voltage,
self-polarizing (faulted) voltage and cross-polarizing voltages (healthy voltages).
The polarizing method is defined with the
346
U_A_AB
U_B_BC
U_C_CA
U3P
U
1
U
2
I_A
I_B
I3P
I_C
I
2
BLOCK
Description
The function can work with any two phase
voltage channels connected but it is recom-
mended to connect all three voltage chan-
nels.
Directional
Phase
calculation
selection
logic
Level
detector
Blocking
logic
Pol quantity setting.
1MRS759142 F
Operation setting. The
Timer
t
OPERATE
t
FAULT_DIR
DIRECTION
Technical Manual
START
REX640