ABB RELION REX640 Technical Manual page 449

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 519: EFHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate
20...60000
time
Reset delay time
0...60000
Measurement
1=RMS
mode
2=DFT
3=Peak-to-Peak
EFIPTOC Settings
Table 520: EFIPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
1.00...40.00
Start value Mult
0.8...10.0
Operate delay time
20...300000
Table 521: EFIPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 522: EFIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.2.1.11
Monitored data
EFLPTOC Monitored data
Table 523: EFLPTOC Monitored data
Name
Type
START_DUR
FLOAT32
EFLPTOC
Enum
REX640
Technical Manual
Unit
Step
0.0001
0.01
0.01
0.1
Unit
Step
ms
1
ms
1
Unit
Step
xIn
0.01
0.1
ms
10
Unit
Step
Unit
Step
ms
1
Values (Range)
0.00...100.00
1=on
2=blocked
3=test
Protection functions
Default
0.1217
2.00
29.10
1.0
Default
20
20
2=DFT
Default
1.00
1.0
20
Default
1=on
Default
20
Unit
Description
%
Ratio of start time / op-
erate time
Status
Description
Parameter B for
customer program-
mable curve
Parameter C for
customer program-
mable curve
Parameter D for
customer program-
mable curve
Parameter E for
customer program-
mable curve
Description
Minimum operate
time for IDMT
curves
Reset delay time
Selects used meas-
urement mode
Description
Start value
Multiplier for scal-
ing the start value
Operate delay time
Description
Operation Off / On
Description
Reset delay time
449