1MRS759142 F
Figure 524: Average operate time of DSTPDIS according to IEC 60255-121 network
models Short line and Long line (50 Hz)
SIR curves are plotted from the data which includes variation of fault location (0...
100% of zone reach, 5% step), fault type (LN, LL, LLN, LLL) and fault inception angle
(0, 30, 60, 90 degrees). Each combination has been repeated ten times giving the
total number of 26880 shots. The operate times include the delay of relay output
contacts. The SIR curves presented in
power outputs (SPOs) and with
4.7.1.4
Analog channel configuration
DSTPDIS has five analog group inputs which must be properly configured.
Table 904: Analog inputs
Input
I3P
I3P_PAR
I3P_REF
Table continues on the next page
1
Can be connected to GRPOFF if
2
Can be connected to GRPOFF if
REX640
Technical Manual
1
2
Par line Comp zone x is set to False.
EF detection Mod GFC is not set to "Io AND IoRef"
Figure 524
were obtained using the static
Zone timer mode = "common".
Description
Three-phase currents
Three-phase currents
Necessary when
to True
Three-phase currents
Protection functions
Par line Comp zone x is set