ABB RELION REX640 Technical Manual page 899

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
Leakage React
0.0...50.0
Voltage Max Cont
80...160
Table 848: OEPVPH Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Minimum operate
200...60000
time
4.5.7.10
OEPVPH Monitored data
Table 849: OEPVPH Monitored data
Name
Type
START_DUR
FLOAT32
T_ENARESTART
INT32
VOLTPERHZ
FLOAT32
OEPVPH
Enum
4.5.7.11
Technical data
Table 850: OEPVPH Technical data
Characteristic
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Table continues on the next page
1
Includes the delay of the signal output contact
REX640
Technical Manual
Unit
%
%
Unit
ms
ms
Values (Range)
0.00...100.00
0...10000
0.00...10.00
1=on
2=blocked
3=test
4=test/blocked
5=off
1
Step
Default
0.1
0.0
1
110
Step
Default
10
100
10
200
Unit
%
s
pu
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±3.0% of the set value
Frequency change:
Typically 200 ms
Voltage change:
Typically 40 ms
Typically 40 ms
Typically 0.96
<35 ms
Protection functions
Description
Leakage reactance
of the machine
Maximum allowed
continuous operat-
ing voltage ratio
Description
Resetting time of
the operate time
counter in DT mode
Minimum operate
time for IDMT
curves
Description
Ratio of start time / op-
erate time (in %)
Estimated time to reset
of block restart
Excitation level, i.e U/f
ratio or Volts/Hertz
Status
899