Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.2.1.10
Settings
EFLPTOC Settings
Table 512: EFLPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
0.010...10.000
Start value Mult
0.8...10.0
Time multiplier
0.025...15.000
Operate delay time
40...300000
Operating curve
1=ANSI Ext. inv.
type
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Table 513: EFLPTOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Table 514: EFLPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Table continues on the next page
REX640
Technical Manual
Unit
Step
xIn
0.005
0.1
0.005
ms
10
Unit
Step
Unit
Step
0.0001
0.0001
0.01
Protection functions
Default
Description
0.010
Start value
1.0
Multiplier for scal-
ing the start value
1.000
Time multiplier
in IEC/ANSI IDMT
curves
40
Operate delay time
15=IEC Def. Time
Selection of time
delay curve type
Default
Description
1=Immediate
Selection of reset
curve type
Default
Description
1=on
Operation Off / On
28.2000
Parameter A for
customer program-
mable curve
0.1217
Parameter B for
customer program-
mable curve
2.00
Parameter C for
customer program-
mable curve
447