Binary Input Inversion - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
1
2
3
Figure 58: Binary input filtering
At the beginning, the input signal is at the high state, the short low state is filtered
and no input state change is detected. The low state starting from the time t
exceeds the filter time, which means that the change in the input state is detected
and the time tag attached to the input change is t
is detected and the time tag t
Each binary input has a filter time parameter
of the binary input of the module in question (for example
Table 97: Input filter parameter values
Parameter
Input # filter time
3.13.4

Binary input inversion

The parameter
Table 98: Binary input states
Control voltage
No
Yes
No
Yes
When a binary input is inverted, the state of the input is TRUE (1) when no control
voltage is applied to its terminals. Accordingly, the input state is FALSE (0) when a
control voltage is applied to the terminals of the binary input.
162
1
3
4
5
t
0
t
1
Input signal
Input # invert is used to invert a binary input.
2
5
4
Filtered input signal
5
Filter time
is attached.
1
"Input # filter" , where # is the number
Values
5...1000 ms
Input # invert
0
0
1
1
1MRS759142 F
. The high state starting from t
0
"Input 1 filter" ).
Default
5 ms
State of binary input
FALSE (0)
TRUE (1)
TRUE (1)
FALSE (0)
Technical Manual
0
1
REX640