ABB RELION REX640 Technical Manual page 367

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Name
Type
DPHHPDOC Monitored data
Table 411: DPHHPDOC Monitored data
Name
Type
START_DUR
FLOAT32
DIR_A
Enum
DIR_B
Enum
DIR_C
Enum
ANGLE_A
FLOAT32
ANGLE_B
FLOAT32
ANGLE_C
FLOAT32
VMEM_USED
BOOLEAN
DPHHPDOC
Enum
4.1.2.12
Technical data
Table 412: DPHxPDOC Technical data
Characteristic
Operation accuracy
Table continues on the next page
REX640
Technical Manual
Values (Range)
4=test/blocked
5=off
Values (Range)
0.00...100.00
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
-180.00...180.00
-180.00...180.00
-180.00...180.00
0=False
1=True
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
DPHLPDOC
Depending on the frequency of the current/voltage
measured: f
Current:
±1.5% of the set value or ±0.002 × I
Voltage:
±1.5% of the set value or ±0.002 × U
Protection functions
Unit
Description
Unit
Description
%
Ratio of start time / op-
erate time
Direction phase A
Direction phase B
Direction phase C
deg
Calculated angle differ-
ence, Phase A
deg
Calculated angle differ-
ence, Phase B
deg
Calculated angle differ-
ence, Phase C
Voltage memory in use
status
Status
±2 Hz
n
n
n
367