ABB RELION REX640 Technical Manual page 137

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
IEC 61850
remote
Figure 51: Station authority is "L,R"
When station authority level "L,R" is used, control access can be selected using R/L
button or CONTROL function block. IEC 61850 data object CTRL.LLN0.LocSta and
CONTROL function block inputs CTRL_STA and CTRL_ALL are not applicable for this
station authority level.
Table 71: Station authority level "L,R" using R/L button
L/R control
R/L button
CTRL.LLN0.LocSta
Local
N/A
Remote
N/A
Off
N/A
Table 72: Station authority "L,R" using CONTROL function block
L/R control
Control FB input
CTRL.LLN0.LocSta
CTRL_OFF
N/A
CTRL_LOC
N/A
CTRL_STA
N/A
CTRL_REM
N/A
CTRL_ALL
N/A
1
Client IEC 61850 command originator category check is not performed.
2
Client IEC 61850 command originator category check is not performed.
REX640
Technical Manual
REMOTE
LOCAL
IEC 61850
IEC 61850
remote
remote
IED
IED
L/R control status
CTRL.LLN0.MltLev
FALSE
FALSE
FALSE
L/R control status
CTRL.LLN0.MltLev
FALSE
FALSE
FALSE
FALSE
FALSE
OFF
IEC 61850
IEC 61850
IEC 61850
remote
remote
remote
IED
L/R state
CTRL.LLN0.LocKey
HMI
1
2
0
L/R state
CTRL.LLN0.LocKey
HMI
0
1
0
2
0
Basic functions
Control access
Local user
IEC 61850 client
x
Control access
Local user
IEC 61850 client
x
1
x
2
x
137

Advertisement

Table of Contents