Basic functions
3.8.9

Signals

Table 80: CONTROL Input signals
Name
CTRL_OFF
CTRL_LOC
CTRL_STA
CTRL_REM
CTRL_ALL
Table 81: CONTROL Output signals
Name
OFF
LOCAL
STATION
REMOTE
ALL
BEH_BLK
BEH_TST
3.8.10

Settings

Table 82: Non group settings
Parameter
Values (Range)
LR control
1=LR key
2=Binary input
Station authority
1=L,R
2=L,S,R
3=L,R,L+R
4=L,S,S+R,L+S,L +S+R
Control mode
1=On
2=Blocked
5=Off
142
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
Default
1=LR key
1=L,R
1=On
Default
Description
0
Control input OFF
0
Control input Local
0
Control input Station
0
Control input Remote
0
Control input All
Description
Control output OFF
Control output Local
Control output Station
Control output Remote
Control output All
Logical device CTRL block status
Logical device CTRL test status
Description
LR control through LR key or bi-
nary input
Control command originator cat-
egory usage
Enabling and disabling control