1MRS759142 F
The recording function of IFPTOC includes recorded data 1 data objects as shown in
Table 636
Table 636: Recorded data 1 data objects of the IFPTOC function
Parameter name
Triggering time
Residual voltage
Residual current
Touch voltage
Touch voltage rms
Fault current
Fault current rms
Start duration
Faulted phase
Fault resistance
Transient Ris Comp
Transient React Comp
Non qualified Harmon
EF indication
Valid EF detection
XC fault detection
Time left to operate
Intermittent EF Det
Started timers
Operated timers
Operate time
A total of two sets of recorded data are saved in data banks
Recorded data 2 . Data bank Recorded data 1 holds the most recent recorded data
and the older data is moved into the data bank
occurs. When all two banks have data and a new triggering occurs, the latest
data is placed into bank
is overwritten by the data from bank
It is possible to reset corresponding recorded data by either:
• activating LHMI parameter Clear/Clear/IFPTOCx reset = 1 ("Clear") or
• writing directly by MMS LD0.IFPTRCx.RcdRs.Oper.ctlVal = 1 ("Clear")"
REX640
Technical Manual
Activation of OPERATE output results to automatic triggering of fault
recording.
.
Parameter description
Triggering time
Residual voltage magnitude [xUn]
Residual current magnitude [xIn]
Touch voltage magnitude [V]
Touch voltage magnitude incl harmonics [V]
Fault current magnitude (incl. reduction) [A]
Fault current magnitude incl harmonics (and reduc-
tion) [A]
Start duration [%]
Faulted phase
Fault point resistance [in primary ohm]
Transient resistive component [A]
Transient reactive component [A]
Non qualified harmonics
Non-directional earth fault detection
Valid EF detection in protected feeder
Cross-country fault detection
Time left to operate [sec.]
Restriking (intermittent) earth fault detection
Started timers
Operated timers
Actual operate time [sec]
Recorded data 1 and the data in bank Recorded data 2
Recorded Data DO
(Timestamp) IF1RFRCx.TchV.t.
(MX) IF1RFRCx.VRes.mag.f
(MX) IF1RFRCx.ARes.mag.f
(MX) IF1RFRCx.TchV.mag.f
(MX) IF1RFRCxTchVRms.mag.f
(MX)) IF1RFRCx.FltA.res.cVal.mag.f
(MX) IF1RFRCx.FltARms.mag.f
(MX) IF1RFRCx.StrDur.mag.f
(ST) IF1RFRCx.FltLoop.stVal
(MX) IF1RFRCx.FltPtRis.mag.f
(MX) IF1RFRCx.AResReal.mag.f
(MX) IF1RFRCx.AResImag.mag.f
(ST) IF1RFRCx.NonQualH.stVal
(ST) IF1RFRCx.EFDet.stVal
(ST) IF1RFRCx.EFDetVald.stVal
(ST) IF1RFRCx.XcnDet.stVal
(MX) IF1RFRCx.TmOpEst.mag.f
(ST) IF1RFRCx.ItmEFInd.stVal
(ST) IF1RFRCx.ActStrSt.stVal
(ST) IF1RFRCx.ActOpSt.stVal
(MX) IF1RFRCx.StrOpTm.mag.f
Recorded data 2 when triggering
Recorded data 1 .
Protection functions
Recorded data 1 and
637