Protection functions
4.2.2.13
Monitored data
DEFLPDEF Monitored data
Table 551: DEFLPDEF Monitored data
Name
Type
START_DUR
FLOAT32
ANGLE_RCA
FLOAT32
ANGLE
FLOAT32
I_OPER
FLOAT32
DEFLPDEF
Enum
DEFHPDEF Monitored data
Table 552: DEFHPDEF Monitored data
Name
Type
START_DUR
FLOAT32
ANGLE_RCA
FLOAT32
ANGLE
FLOAT32
I_OPER
FLOAT32
DEFHPDEF
Enum
4.2.2.14
Technical data
Table 553: DEFxPDEF Technical data
Characteristic
Operation accuracy
Table continues on the next page
480
Values (Range)
0.00...100.00
-180.00...180.00
-180.00...180.00
0.00...40.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Values (Range)
0.00...100.00
-180.00...180.00
-180.00...180.00
0.00...40.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
current: f
DEFLPDEF
Current:
±1.5% of the set value or ±0.002 × I
Unit
Description
%
Ratio of start time / op-
erate time
deg
Angle between operat-
ing angle and charac-
teristic angle
deg
Angle between polar-
izing and operating
quantity
xIn
Calculated operating
current
Status
Unit
Description
%
Ratio of start time / op-
erate time
deg
Angle between operat-
ing angle and charac-
teristic angle
deg
Angle between polar-
izing and operating
quantity
xIn
Calculated operating
current
Status
±2 Hz
n