ABB RELION REX640 Technical Manual page 489

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.2.3.8
INTRPTEF Settings
Table 559: INTRPTEF Group settings (Basic)
Parameter
Values (Range)
Directional mode
1=Non-directional
2=Forward
3=Reverse
Operate delay time
40...1200000
Voltage start value
0.05...0.50
Table 560: INTRPTEF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Operation mode
1=Intermittent EF
2=Transient EF
Table 561: INTRPTEF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
40...60000
Peak counter limit
2...20
Min operate current 0.01...1.00
4.2.3.9
INTRPTEF Monitored data
Table 562: INTRPTEF Monitored data
Name
Type
FAULT_DIR
Enum
START_DUR
FLOAT32
INTRPTEF
Enum
REX640
Technical Manual
Unit
Step
ms
10
xUn
0.01
Unit
Step
Unit
Step
ms
1
1
xIn
0.01
Values (Range)
0=unknown
1=forward
2=backward
3=both
0.00...100.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection functions
Default
2=Forward
500
0.20
Default
1=on
1=Intermittent EF
Default
500
2
0.01
Unit
Description
Detected fault direction
%
Ratio of start time / op-
erate time
Status
Description
Directional mode
Operate delay time
Voltage start value
Description
Operation Off / On
Operation criteria
Description
Reset delay time
Min requirement
for peak counter
before start in IEF
mode
Minimum operating
current for transi-
ent detector
489