ABB RELION REX640 Technical Manual page 900

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Characteristic
Operate time accuracy in definite-time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse-time mode
4.5.8
Low-voltage ride-through protection LVRTPTUV (ANSI
27RT)
4.5.8.1
Identification
Function description
Low-voltage ride-through protec-
tion
4.5.8.2
Function block
Figure 502: Function block
4.5.8.3
Functionality
The low-voltage ride-through protection function LVRTPTUV is principally a
three-phase undervoltage protection. It differs from the traditional three-phase
undervoltage protection PHPTUV by allowing the grid operators to define its own
Low-Voltage Ride-Through ( LVRT) curve for generators, as defined by local or
national grid codes. The LVRT curve can be defined accurately according to the
requirements by setting the appropriate time-voltage coordinates.
This function contains a blocking functionality. LVRTPTUV can be blocked with the
BLOCK input. Blocking resets timers and outputs.
4.5.8.4
Analog channel configuration
LVRTPTUV has one analog group input which must be properly configured.
Table 851: Analog inputs
Input
U3P
There are a few special conditions which must be noted with the configuration.
900
See the preprocessing function blocks in this document for the possible
signal sources.
Value
±5.0% of the theoretical value or ±50 ms
IEC 61850
IEC 60617
identification
identification
LVRTPTUV
U<RT
Description
Three-phase voltages
1MRS759142 F
ANSI/IEEE C37.2
device number
27RT
REX640
Technical Manual