Advertisement

Protection functions
Load-shedding steps
4
5
4.6.2.7
Signals
LSHDPFRQ Input signals
Table 896: LSHDPFRQ Input signals
Name
U3P
BLOCK
BLK_REST
MAN_RESTORE
LSHDPFRQ Output signals
Table 897: LSHDPFRQ Output signals
Name
OPERATE
OPR_FRQ
OPR_FRG
START
ST_FRQ
ST_FRG
RESTORE
ST_REST
4.6.2.8
LSHDPFRQ Settings
Table 898: LSHDPFRQ Group settings (Basic)
Parameter
Values (Range)
Load shed mode
1=Freq<
6=Freq< OR df/dt
Table continues on the next page
938
Restore start Val setting
0.990 · Fn (49.5 Hz)
0.990 · Fn (49.5 Hz)
Type
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
Restore delay time setting
50000 ms
10000 ms
Default
Description
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
0=False
Block restore
0=False
Manual restore signal
Description
Operation of load shedding
Operate signal for under fre-
quency
Operate signal for high df/dt
Start
Pick-Up signal for under fre-
quency detection
Pick-Up signal for high df/dt
detection
Restore signal for load restor-
ing purposes
Restore frequency attained
and restore timer started
Default
1=Freq<
1MRS759142 F
Description
Set the operation
mode for load
shedding function
REX640
Technical Manual