• Area B defines the linear growth recovery voltage level from
Voltage level 2 in a time period from Recovery time 1 to Recovery time 2 .
• Area C is the zone where voltage stabilizes.
value as
period from
The system restores to a normal state and function resets when the voltage is equal
or greater than
When the voltage at the point of common coupling is above the LVRT curve, the
generation unit must remain connected, and must be disconnected only if the
voltage takes values below the curve.
Figure 507: A typical required ride-through voltage capability of generating unit
The LVRT requirement depends on the power system characteristics and the
protection employed, varying significantly from each other. The requirement also
differs from country to country. LVRTPTUV function incorporates four types of LVRT
curves which satisfy most of the power system needs. Grid operators can fine-tune
the LVRT curve by setting the parameters as per their requirement, making the
use simpler in comparison with different conventional undervoltage protection with
different operate time setting and logics.
4.5.8.7
Signals
LVRTPTUV Input signals
Table 854: LVRTPTUV Input signals
Name
U3P
BLOCK
REX640
Technical Manual
Voltage level 2 . The system should remain above this voltage in a time
Recovery time 2 to Recovery time 3 .
Voltage level 4 after Recovery time 4 time period.
Type
SIGNAL
BOOLEAN
Protection functions
Voltage level 1 to
Voltage level 3 is defined to same
Default
Description
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode