ABB RELION REX640 Technical Manual page 771

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.3.5.10
Signals
HREFPDIF Input signals
Table 689: HREFPDIF Input signals
Name
IRES
BLOCK
HREFPDIF Output signals
Table 690: HREFPDIF Output signals
Name
OPERATE
START
4.3.5.11
Settings
HREFPDIF Settings
Table 691: HREFPDIF Group settings (Basic)
Parameter
Values (Range)
Operate value
1.0...50.0
Minimum operate
20...300000
time
Table 692: HREFPDIF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 693: HREFPDIF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.3.5.12
Monitored data
REX640
Technical Manual
Type
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
%In
0.1
ms
1
Unit
Step
Unit
Step
ms
1
Protection functions
Default
Description
-
Residual current
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Default
5.0
20
Default
1=on
Default
20
Description
Low operate value,
percentage of the
nominal current
Minimum operate
time
Description
Operation Off / On
Description
Reset delay time
771