ABB RELION REX640 Technical Manual page 401

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
JAMPTOC Output signals
Table 454: JAMPTOC Output signals
Name
OPERATE
4.1.7.8
JAMPTOC Settings
Table 455: JAMPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Start value
0.10...10.00
Operate delay time
100...120000
Table 456: JAMPTOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.1.7.9
JAMPTOC Monitored data
Table 457: JAMPTOC Monitored data
Name
Type
START
BOOLEAN
START_DUR
FLOAT32
JAMPTOC
Enum
4.1.7.10
Technical data
Table 458: JAMPTOC Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Table continues on the next page
REX640
Technical Manual
Type
BOOLEAN
Unit
Step
xIn
0.01
ms
10
Unit
Step
ms
1
Values (Range)
0=False
1=True
0.00...100.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection functions
Description
Operate
Default
1=on
2.50
2000
Default
100
Unit
%
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
Typically 40 ms
Typically 0.96
Description
Operation Off / On
Start value
Operate delay time
Description
Reset delay time
Description
Start
Ratio of start time / op-
erate time
Status
n
401