ABB RELION REX640 Technical Manual page 396

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
T2PTTR Input signals
Table 444: T2PTTR Input signals
Name
I3P
BLOCK
AMB_TEMP
T2PTTR Output signals
Table 445: T2PTTR Output signals
Name
OPERATE
START
ALARM
BLK_CLOSE
4.1.6.8
T2PTTR Settings
Table 446: T2PTTR Group settings (Basic)
Parameter
Values (Range)
Env temperature
-50...100
Set
Temperature rise
0.0...200.0
Max temperature
22.0...200.0
Operate tempera-
80.0...120.0
ture
Alarm temperature
40.0...100.0
Reclose tempera-
40.0...100.0
ture
Short time con-
6...60000
stant
Long time constant 60...60000
Weighting factor p
0.00...1.00
396
Type
SIGNAL
BOOLEAN
FLOAT32
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
°C
1
°C
0.1
°C
0.1
%
0.1
%
0.1
%
0.1
s
1
s
1
0.01
Default
Description
-
Three-phase currents
0=False
Block signal for acti-
vating the blocking
mode
0
The ambient temper-
ature used in the cal-
culation
Description
Operate
Start
Thermal Alarm
Thermal overload indicator.
To inhibite reclose.
Default
40
78.0
105.0
100.0
90.0
60.0
450
7200
0.40
1MRS759142 F
Description
Ambient tempera-
ture used when
no external temper-
ature measurement
available
End temperature
rise above ambient
Maximum tempera-
ture allowed for the
transformer
Operate tempera-
ture, percent value
Alarm temperature,
percent value
Temperature for re-
set of block reclose
after operate
Short time con-
stant in seconds
Long time constant
in seconds
Weighting factor of
the short time con-
stant
REX640
Technical Manual