Basic functions
Time settings
Table 57: Non group settings
Parameter
Values (Range)
Synch source
0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
17=IEC60870-5-103
PTP Profile
1=IEEE
C37.238-2011
2=IEC 61850-9-3
PTP domain ID
0...255
PTP priority 1
0...255
PTP priority 2
0...255
PTP Slave-only
0=False
1=True
Time master mode
1=Master with fi-
nite holdover
2=Master with in-
finite holdover
Clear clock list
0=False
1=True
Time Syn Src Tmm
1...65535
Table 58: Non group settings
Parameter
Values (Range)
Date
Time
Local time offset
-840...840
Table 59: Non group settings
Parameter
Values (Range)
IP SNTP primary
IP SNTP secondary
128
Unit
Step
1
1
1
min
1
Unit
Step
min
1
Unit
Step
1MRS759142 F
Default
Description
1=SNTP
Time synchroniza-
tion source
1=IEEE
Profile Selection for
C37.238-2011
the Precision Time
Protocol
0
The domain is iden-
tified by an inte-
ger, the domain-
Number, in the
range of 0 to 255.
128
PTP priority 1, in
the range of 0 to
255.
128
PTP priority 2, in
the range of 0 to
255.
0=False
If true, the IED can-
not become a clock
master
1=Master with fi-
Device Time Master
nite holdover
Mode
0=False
Clears the stored
master clock list
3
Time synchroniza-
tion timeout for
legacy protocols as
clock source (Mod-
bus, IEC103, IEC101,
IEC104 and DNP)
Default
Description
0
Date
0
Time
0
Local time offset in
minutes
Default
Description
192.168.2.166
IP address for SNTP
primary server
192.168.2.165
IP address for SNTP
secondary server
Technical Manual
REX640