Settings; Local/Remote Control Control; Function Block; Functionality - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Name
GRPOFF
DEV_WARN
FRQ_ADP_WARN
FRQ_ADP_FAIL
FRQ_ADP_BU
3.7.4

Settings

Table 69: PROTECTION Settings
Parameter
Values (Range)
SG operation mode
1=Operator
2=Logic mode 1
3=Logic mode 2
3.8

Local/Remote control CONTROL

3.8.1

Function block

Figure 50: Function block
3.8.2

Functionality

Local/Remote control is by default realized through the R/L button on the front
panel. The control via binary input can be enabled by setting the value of the
LR control setting to "Binary input". The binary input control requires that the
CONTROL function is instantiated in the product configuration.
Local/Remote control supports multilevel access for control operations in
substations according to the IEC 61850 standard. Multilevel control access with
separate station control access level is not supported by other protocols than IEC
61850.
The actual Local/Remote control state is evaluated by the priority scheme on the
function block inputs. If more than one input is active, the input with the highest
priority is selected. The priority order is "off", "local", "station", "remote", "all".
REX640
Technical Manual
Type
Group signal
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
Default
1=Operator
Description
Group off signal for function blocks
Protection relay internal warning
Frequency adaptivity warning
Frequency adaptivity status fail
Main frequency adaptivity source
Description
Operation mode for setting
group change
Basic functions
135

Advertisement

Table of Contents
loading

Table of Contents