Basic functions
3.14.1
Power output contacts
Power output contacts are normally used for energizing the breaker closing coil and
trip coil, external high burden lockout or trip relays.
3.14.1.1
Dual single-pole power outputs POSP1 and POSP2
Dual (series-connected) single-pole (normally open/form A) power output contacts
POSP1 and POSP2 are rated for continuous current of 8 A. The contacts are normally
used for closing circuit breakers and energizing high burden trip relays. They can be
arranged to trip the circuit breakers when the trip circuit supervision is not available
or when external trip circuit supervision relay is provided.
The power outputs are included in the power supply module in slot G.
Figure 59: Dual single-pole power outputs in power supply module
3.14.1.2
Double-pole power outputs PODP1, PODP2 and PODP3 with trip
circuit supervision
The power outputs PODP1, PODP2 and PODP3 are double-pole normally open/
form A power outputs with trip circuit supervision. The trip circuit supervision
hardware includes constant current generator to provide trip circuit supervision
(TCS) current and TCS input that can be connected to the TCS function with
Application Configuration in PCM600. See Trip circuit supervision TCSSCBR function
for TCS connections.
When the two poles of the contacts are connected in series, they have the same
technical specification as POSP1/POSP2 for breaking duty. Contacts PODP1, PODP2
and PODP3 are usually used for energizing the breaker trip coils.
The power outputs are included in the power supply module in slot G.
164
1MRS759142 F
REX640
Technical Manual