1MRS759142 F
3.4.1

Function block

Figure 39: Function block
3.4.2

Functionality

The protection relay includes a global conditioning function LEDPTRC that is used to
control the virtual Start and Trip indication LEDs.
LED indication control is preconfigured in a such way that all the protection
function general start and operate signals are combined with this function
(available as output signals OUT_START and OUT_OPERATE). These signals are
internally connected to Device Status on WHMI Dashboard and the Device Status
widget on the LHMI if the widget has been instantiated in the LHMI engineering
phase. LEDPTRC collects and combines phase information from different protection
functions (available as output signals OUT_ST_A /_B /_C and OUT_OPR_A /_B /
_C). There is also combined earth fault information collected from all the earth-
fault functions available in the relay configuration (available as output signals
OUT_ST_NEUT and OUT_OPR_NEUT).
3.5

Individual virtual LED control LED

3.5.1

Identification

Function description
Individual virtual LED control
REX640
Technical Manual
LED indication control should never be used for tripping purposes.
There is a separate trip logic function TRPPTRC available in the relay
configuration.
IEC 61850
IEC 60617
identification
identification
LED
LED
Basic functions
ANSI/IEEE
identification
LED
117