1MRK 511 401-UUS A
Section 7
7.1
7.1.1
7.1.2
Bay control REC670 2.2 ANSI
Application manual
Differential protection
High impedance differential protection, single phase
HZPDIF (87)
Identification
Function description
High impedance differential protection,
single phase
Application
The 1Ph High impedance differential protection function HZPDIF (87) can be used as:
•
Generator differential protection
•
Reactor differential protection
•
Busbar differential protection
•
Autotransformer differential protection (for common and serial windings only)
•
T-feeder differential protection
•
Capacitor differential protection
•
Restricted ground fault protection for transformer, generator and shunt reactor
windings
•
Restricted ground fault protection
The application is dependent on the primary system arrangements and location of
breakers, available CT cores and so on.
Differential protection
IEC 61850
IEC 60617
identification
identification
HZPDIF
Id
SYMBOL-CC V2 EN-US
Section 7
IP14239-1 v4
M14813-1 v4
ANSI/IEEE C37.2
device number
87
IP14944-1 v3
SEMOD54734-4 v8
127