Liquid medium supervision SSIML (71)

Identification
Function description
Insulation liquid monitoring function
Application
Liquid medium supervision (SSIML ,71) is used for monitoring the transformers and
tap changers. When the level becomes too low compared to the required value, the
operation is blocked to minimize the risk of internal failures. Binary information based
on the oil level in the transformer and the tap changer is used as input signals to the
function. In addition to that, the function generates alarms based on received
information.
Setting guidelines
The parameters for Liquid medium supervision SSIML can be set via local HMI or
Protection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of liquid medium supervision
i.e. Off/On.
LevelAlmLimit: This is used to set the limit for a level alarm condition in the
transformer.
LevelLOLimit: This is used to set the limit for a level lockout condition in the
transformer.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in the
transformer.
TempLOLimit: This is used to set the limit for a temperature lockout condition in the
transformer.
tLevelAlarm: This is used to set the time delay for a level alarm indication, given in s.
tLevelLockOut: This is used to set the time delay for a level lockout indication, given
in s.
IEC 61850
IEC 60617
identification
identification
SSIML
-
1MRK 511 401-UUS A
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3
ANSI/IEEE C37.2
device number
71
GUID-140AA10C-4E93-4C23-AD57-895FADB0DB29 v6
GUID-0C8E498B-2A65-44ED-91D6-53EC72F49222 v2
Bay control REC670 2.2 ANSI
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents