Setting Guidelines - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
17.2.3
Bay control REC670 2.2 ANSI
Application manual

Setting guidelines

The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of gas medium supervision i.e.
Off/On.
PresAlmLimit: This is used to set the limit for a pressure alarm condition in the circuit
breaker.
PresLOLimit: This is used to set the limit for a pressure lockout condition in the circuit
breaker.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in the
circuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in the
circuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication, given
in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout indication,
given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set time
delay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set time
delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a set
time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set
time delay in s.