ABB REC670 Applications Manual page 380

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 14
Control
374
Section 1
(WA1)A1
(WA2)B1
(WA7)C
ABC_LINE
ANSI04000479 V1 EN-US
Figure 132:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL
A bus-coupler connection exists between busbar WA1 and WA2.
BC_17_OP
No bus-coupler connection between busbar WA1 and WA7.
BC_17_CL
A bus-coupler connection exists between busbar WA1and WA7.
BC_27_OP
No bus-coupler connection between busbar WA2 and WA7.
BC_27_CL
A bus-coupler connection exists between busbar WA2 and WA7.
VP_BC_12
The switch status of BC_12 is valid.
VP_BC_17
The switch status of BC_17 is valid.
VP_BC_27
The switch status of BC_27 is valid.
EXDU_BC
No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC) are needed:
Signal
BC12CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
BC17OPTR
No bus-coupler connection through the own bus-coupler between busbar WA1 and
WA7.
BC17CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA7.
BC27OPTR
No bus-coupler connection through the own bus-coupler between busbar WA2 and
WA7.
BC27CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA2
and WA7.
VPBC12TR
The switch status of BC_12 is valid.
VPBC17TR
The switch status of BC_17 is valid.
VPBC27TR
The switch status of BC_27 is valid.
EXDU_BC
No transmission error from the bay that contains the above information.
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
ABC_LINE
1MRK 511 401-UUS A
Section 2
A2
B2
C
ABC_BC
en04000479_ansi.vsd
Bay control REC670 2.2 ANSI
Application manual