Function description
Single point generic control 8 signals
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection
of 8 single point commands that can be used for direct commands for example reset of
LED's or putting IED in "ChangeLock" state from remote. In this way, simple
commands can be sent directly to the IED outputs, without confirmation. Confirmation
(status) of the result of the commands is supposed to be achieved by other means, such
as binary inputs and SPGAPC function blocks.
PSTO is the universal operator place selector for all control functions.
Even if PSTO can be configured to allow LOCAL or ALL operator
positions, the only functional position usable with the SPC8GAPC
function block is REMOTE.
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are
set via the local HMI or PCM600.
Operation: turning the function operation Enabled/Disabled.
There are two settings for every command output (totally 8):
PulseModex: decides if the command signal for output x is Latched (steady) or Pulsed.
tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse (in
seconds).
AutomationBits, command function for DNP3.0
AUTOBITS
IEC 61850
IEC 60617
identification
identification
SPC8GAPC
-
Section 14
Control
SEMOD176456-2 v3
ANSI/IEEE C37.2
device number
-
SEMOD176511-4 v6
SEMOD176518-4 v6
SEMOD158589-1 v3
459

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents